TDF15 has an identical to TD15, but with additional 10 kΩ setting knob.
Application
TD11..15 and TDF12..15 are used to measure the room temperature.
The temperature sensors are used in conjunction with all Kieback&Peter loop controllers and control systems that have a sensor connection for the active KP10 measuring element.
Technical Data
Measured quantity: Room temperature in homes or offices.
Measuring tolerance: Typically ±0.2K.
Measuring range: -20 °C to +60 °C.
Plastic housing, RAL 9010 (pure white).
Measuring element: KP10 active measuring element; 2.73 V at 0 °C; TC = 10 mV/K.