Analog control panel are the SA-P20R and SA-P4LR analog addressable FACP supports 2 or 4 SLC loops for a total of 500 primary points or 800 points using subpoints. SLC loop communications uses standard twisted pair cabling, shielded cable is not necessary.
The panel may be configured with various communication cards; communications options support central station monitoring, virtual panel and networking.
Multi-Loop 2 Analog Addressable
Loops Field upgradable to 4
126 primary points per loop
800 points per panel when using devices with sub-points
Up to 10,000 ft. wiring length on SLC loop
64 Panels on a network
Programmable through a PC connection to the panel, or through keypad
Programmable relays – 5
Supervised Powered Outputs – 3
Programmable notification appliance circuits:4
Power per NAC: 1.6 Amps Max
Programmable outputs on SLC loop
Programmable Function button on front display
Power Supply: 5.25 Amp, regulated & integrated
LCD Display: 8x40
Zonal Mode: Annunciation by zone w/o individual relationships
Panel Ring Modes: Common, Zonal, and Stage 2
NAC Outputs programmable as Continuous, March, Temporal
Program cause and effects AND, OR, or any two (Cross Zone)
Battery size: Up to 17 Ah in standard enclosure; up to 52 Ah with external cabinet
Access levels: 3
Access key switch: Yes
Available in Red
Manufacturer: | National Fire Fighting Manufacturing Company |
Country of origin: | UAE |
Certification | UL Listed, FM Approved |